Von Corp., The - Item # XF16-1280v.2, One Piece Cable Fault Locator using Arc Reflection Method
HomeServisavorwww.voncorp.com
Portable DC TestFault Locating SystemsInsulated Glove and Blanket Testing EquipmentBoom Current Monitors, Sphere Gap Voltmeters and Accessories
Training ProgramsShop OnlineSales RepresentativesContact Us
 Search Catalog
      GO   
 All Categories    XF Series of Portable Arc Reflection Systems
View CartView RFQ's  | Shipping 
 | Tax 
 | Terms 
 Shopping Cart  0 items 
 Request for Quote  0 items 
All Categories > VON Accessories > Model B-.35 and B-.45 Series  > XF Series of Portable Arc Reflection Systems > Item # XF16-1280v.2  
Request Information

Item # XF16-1280v.2 One Piece Cable Fault Locator using Arc Reflection Method

QUOTE



    Print Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

XF16-1280v_2

larger image
One Piece Cable Fault Locator using Arc Reflection Method
16kV Fault Locator/Sectionalizer. Simple operation, On, Radar, Start and unit gives distance to the fault. 1280 joules at both 8kV and 16kV. Radar Auto-ranges and Auto-Locates the fault.



 Specifications  

Minimum Order

1

Package Type

Each

Units Per Package

1

Thumper Specifications

1280 joule "dual thump capacitor" provides full energy at 8kV and 16kV. 15 Second thump interval.

Input Power

120V AC
Internal 12V DC Battery
External 12V DC

Leads

50 foot Shielded test lead terminated in male MC Connector, 15 foot #2 ground cable, 10 foot AC Plug, 10 foot battery cable.

Height

48 Inch

Width

29.5 Inch

Weight

230 lb

Environmental

Operation from -10 to 110 Degrees F. Unit sealed for all weather operation.

TDR Specifications

Auto-range, Auto-locate functions standard. Eight Memories. 2.75" x 4.3" LCD with 320x240 dot matrix. Accuracy 0.5% of the range selected. Backlight for night time operation.